A Novel Stabilization Method of LC Input Filter With Constant Power Loads Without Load Performance Compromise in DC Microgrids

Journal

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Volume 62, Issue 7, Pages 4552-4562

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIE.2014.2367005

Keywords

Active-damping methods; constant power loads (CPLs); dc microgrids; virtual resistor

Ask authors/readers for more resources

In dc microgrids, it is common that constant power loads (CPLs) exhibit negative incremental resistance. They degrade the stability margin of operation with their LC input filters and, thus, the whole system. In traditional active-damping methods, the extra stabilizing current is injected into CPLs to modify its input impedance to fulfill stability criteria. However, this injected current may cause undesirable performance of the loads, e.g., fluctuation in rotating speed of tightly regulated motors. There is always a compromise between stability margin and load performances. In order to overcome this drawback, this paper proposes a method that stabilizes the system from source-side converters, instead of from CPL themselves. In the proposed method, a virtual resistance is built in the source-side converter. This virtual resistor is effective around the resonant frequency of the LC input filter and thus can indirectly reduce its output impedance to fulfill Middlebrook's stability criterion. This paper also proves, both analytically and experimentally, that, in dc microgrids, resonant frequencies of LC filters of paralleled CPLs have to be different to maintain system stability. Simulation and experimental results are reported to verify the effectiveness of the proposed idea.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.8
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available