Experimental Study of a House-Hold Dual Evaporation Temperatures Based Chiller

Journal

JOURNAL OF ENGINEERING THERMOPHYSICS
Volume 32, Issue 2, Pages 360-377

Publisher

PLEIADES PUBLISHING INC
DOI: 10.1134/S181023282302011X

Keywords

-

Ask authors/readers for more resources

This paper discusses the indoor environment control strategies in small buildings and proposes a new water chiller based on dual evaporation temperatures, which can be used for temperature and humidity independent control (THIC) in residential buildings. Experimental results show that this novel chiller can maintain high and low water supplying temperatures in varying summer conditions, providing chilled water of two different temperatures. Moreover, the energy efficiency ratio (EER) of the compressor is comparable to conventional DX A/C systems or chillers of the same size, indicating the feasibility of this novel chiller.
Indoor environment control strategies in small buildings are simply considered, such as achieving the indoor temperature control through ON/OFF cycling the compressor of a direct expansion (DX) air conditioning (A/C) system, leaving the indoor humidity uncontrolled. In some areas, the large latent cooling load will lead to an unstable and high indoor humidity, resulting in deteriorating thermal comfort, indoor air quality and energy efficiency, suggesting that an actively controlled humidity is indispensable. The existing temperature and humidity independent control (THIC) methods are too complicated to be suitable for applying in small buildings. Therefore, the authors established a water chiller which can be applied in residential buildings for THIC by using a dual-evaporation-temperature compressor. A prototype was built and experimentally tested. Results showed that in the varying summer condition, the high and low water supplying temperatures were maintained around 18.8 & DEG;C and 7.8 & DEG;C, respectively, suggesting that this novel chiller could provide chilled water of two different temperatures for THIC. Furthermore, the energy efficiency ratios (EER) of the compressor was 3.5, which was comparable to those conventional DX A/C systems or chillers of the same size. Therefore, this novel chiller based on dual evaporation temperatures was feasible.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.3
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available