4.3 Article

Calculation of a Health Index of Oil-Paper Transformers Insulation with Binary Logistic Regression

Journal

MATHEMATICAL PROBLEMS IN ENGINEERING
Volume 2016, Issue -, Pages -

Publisher

HINDAWI LTD
DOI: 10.1155/2016/6069784

Keywords

-

Funding

  1. Science and Technology Project of State Grid Corporation of China (SGCC) [EPRIPDKJ(2014)2863]

Ask authors/readers for more resources

This paper presents a new method for calculating the insulation health index (HI) of oil-paper transformers rated under 110 kV to provide a snapshot of health condition using binary logistic regression. Oil breakdown voltage (BDV), total acidity of oil, 2-Furfuraldehyde content, and dissolved gas analysis (DGA) are singled out in this method as the input data for determining HI. A sample of transformers is used to test the proposed method. The results are compared with the results calculated for the same set of transformers using fuzzy logic. The comparison results show that the proposed method is reliable and effective in evaluating transformer health condition.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.3
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available