4.7 Article

A feedback model to predict parameters for controlling the performance of a mechanical draft cooling tower

Journal

APPLIED THERMAL ENGINEERING
Volume 105, Issue -, Pages 519-530

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2016.03.030

Keywords

Forced draft; L/G ratio; Inverse optimization; Feedback; Tower control

Funding

  1. Indian Institute of Technology Ropar, Punjab

Ask authors/readers for more resources

In this work, a feedback model has been proposed in order to control the performance of a mechanical draft cooling tower under varying heat load conditions suiting diverse applications such as solar power generation, HVAC and diesel engine. The model uses specific objective functions to meet the operating conditions related with the process requirement under varying heat load. These objective functions have been formulated using empirical correlations corresponding to different performance parameters developed from experimental data. Thereafter, an inverse method-based feedback model is made to control the cooling tower's performance for different outputs. The simulated model considers different cases closely relating to practical use of the cooling tower. Further, by monitoring the inlet water temperature with time, the controlling variable governed by water to air ratio has been adjusted to optimize the tower operation. It is concluded that for different situations, the proposed inverse feedback model is an optimized tool to control the tower performance. (C) 2016 Elsevier Ltd. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available