4.1 Article

Optimal use of chlorine in water distribution networks based on specific locations of booster chlorination: analyzing conditions in Mexico

Journal

WATER SCIENCE AND TECHNOLOGY-WATER SUPPLY
Volume 16, Issue 2, Pages 493-505

Publisher

IWA PUBLISHING
DOI: 10.2166/ws.2015.161

Keywords

drinking water quality; extended period; free chlorine; genetic algorithms

Funding

  1. Universidad de Guanajuato (UG) [20113.2013, 391/2014]

Ask authors/readers for more resources

Water distribution networks (WDNs) could present problems of pathogen intrusion that affect the health of consumers. One solution to diminish this risk is to add more disinfectant to the water at the drinking water treatment plant (DWTP). However, this increases the cost of water treatment and may also cause the formation of trihalomethanes. Mexico has the largest bottled water market in the world. Also, most houses are built with individual storage containers due to intermittent service, which generates a greater residence time of the water before use. This paper shows an alternative to guarantee minimum disinfection along WDNs and diminish the use of disinfectant at the DWTP considering the conditions of water consumption and use in Mexico. We propose a model based on Genetic Algorithms to obtain scenarios where free chlorine is maintained at the minimum permissible concentration throughout the day. In addition, Water Managers could optimize the use of disinfectant by implementing booster chlorination stations (BCSs). The results show that chlorine use could be reduced by 38%, therefore guaranteeing the chlorine concentration limits along the WDN.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.1
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available