Journal
JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY
Volume 32, Issue 9, Pages 4535-4543Publisher
KOREAN SOC MECHANICAL ENGINEERS
DOI: 10.1007/s12206-018-0850-0
Keywords
Corrugated tube; Steam condenser; Titanium; Heat transfer coefficient; Friction factor
Categories
Funding
- Incheon National University
Ask authors/readers for more resources
Usage of enhanced tubes in electric utility steam condensers have many advantages including smaller condenser size, additional electricity generation by lowered condenser back pressure, etc. In the present study, titanium corrugated tubes were tested for application to electric utility steam condensers. The tubes have relatively small corrugation heights and large corrugation pitches. In addition, the lowest helix angle is 18o, which is much lower than those of existing studies. The friction factor increased as corrugation pitch decreased and corrugation height increased. The penalty factor ranged from 1.09 to 1.89. The heat transfer coefficients showed similar trend with that of the friction factor. The enhancement factor ranged from 1.05 to 1.46. Exiting correlations did not adequately predict the present friction factors and heat transfer coefficients. The reason was attributed to the geometric difference of the present corrugated tubes (large p/e and small e/D-i). New correlations were developed, which predicted the present data within +/- 20 %.
Authors
I am an author on this paper
Click your name to claim this paper and add it to your profile.
Reviews
Recommended
No Data Available