Journal
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
Volume 35, Issue 7, Pages 1869-1877Publisher
ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2012.05.013
Keywords
Two-phase flow; Refrigerant distribution; Microchannel evaporator; Air-conditioning system
Categories
Funding
- Air Conditioning and Refrigeration Center (ACRC) at the University of Illinois
Ask authors/readers for more resources
This paper demonstrates that the performance of a mobile air conditioning system (with a microchannel evaporator modified to be single pass) operating normally with R134a in direct expansion mode can be significantly improved when switched to flash gas bypass (FGB) mode. When operated at the same compressor speed, the system in FGB mode produces about 13%-18% more cooling capacity at 4%-7% higher COP than DX mode. When the compressor speed was adjusted to maintain the same cooling capacity, the COP improved 37%-55%. Two main reasons are identified and discussed: 1) improved refrigerant distribution and 2) reduction of refrigerant pressure drop. Published by Elsevier Ltd.