4.5 Article

Comparison of PIV and PDA droplet velocity measurement techniques on two high-pressure water mist nozzles

期刊

FIRE SAFETY JOURNAL
卷 44, 期 8, 页码 1030-1045

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.firesaf.2009.07.003

关键词

Water mist; PIV; PDA; High-pressure nozzles; Spray; Measurements

向作者/读者索取更多资源

The need for reliable measurement of droplet velocities and droplet size has increased with the more widespread use of water mist systems. Two optical measuring techniques have been investigated, Particle Image Velocimetry (PIV) and phase Doppler anemometry (PDA). Measurements have been performed on two high-pressure nozzles, a hollow cone nozzle and a full cone nozzle. Both methods performed well close to the nozzle and further away from the nozzle. In the intermediate region the results obtained with PIV are biased against the larger droplets. The two methods complement each other, PIV giving the instantaneous velocity field and PDA giving both the droplet velocity and droplet size at a point. The measurement indicates that higher throw length can be archived with a full cone nozzle compared to the hollow cone nozzle, if both nozzles have the same cone angle and flow rate. (C) 2009 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据