期刊
EXPERIMENTAL THERMAL AND FLUID SCIENCE
卷 54, 期 -, 页码 304-312出版社
ELSEVIER SCIENCE INC
DOI: 10.1016/j.expthermflusci.2014.01.007
关键词
Carbon dioxide; Supercritical; Gas cooler; Tube-in-tube heat exchanger
资金
- Energy R&D foundation from the Bureau of Energy of the Ministry of Economic, Taiwan
- National Science Council [102-ET-E-009-006-ET]
In this study, investigation of the performance of a tube-in-tube counter-flow water-cooled CO2 gas cooler operating above and near critical pressure is presented using a heat pump water heater with CO2 flowing in the annulus side. A tube-in-tube heat exchanger model applicable for supercritical fluid CO2 and water was also developed and validated. The measured total heat transfer capacity ranged from 1.31 to 4.06 kW at various test conditions. The calculations show good agreement with the experimental results. The results demonstrate that the variation of CO2 temperature tends to show very slow decreasing near the pseudo-critical region when compared to the inlet region. Yet this phenomenon becomes more pronounced as the inlet pressure is close to the critical pressure (73.8 bar). The calculation also reveals a peculiar phenomenon that the local heat transfer rate of the heat exchanger peaks within the heat exchanger near the pseudo critical region due to the drastic rise of specific heat (C-p value). (C) 2014 Elsevier Inc. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据