期刊
ENERGY CONVERSION AND MANAGEMENT
卷 49, 期 11, 页码 3343-3348出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2007.09.033
关键词
Absorption cooler; H2O-LiBr; Double effect; Energy; Exergy; Modelling
In this paper, exergy analysis of double effect lithium bromide/water absorption refrigeration system is presented. The system consists of a second effect generator between the generator and condenser of the single effect absorption refrigeration system, including two solution heat exchangers between the absorber and the two generators. In order to simulate the refrigeration system by using a computer, a new set of computationally efficient formulations of thermodynamic properties of lithium bromide/water solution developed is used. The exergy analysis is carried out for each component of the system. All exergy losses that exist in double effect lithium bromide/water absorption system are calculated. In addition to the coefficient of performance and the exergetic efficiency of the system, the number of exergy of each component of the system is also estimated. This study suggests the component of the absorption refrigeration system that should be developed. The results show that the performance of the system increases with increasing low pressure generator (LPG) temperature, but decreases with increasing high pressure generator (HPG) temperature. The highest exergy loss occurs in the absorber and in the HPG, which therefore makes the absorber and HPG the most important components of the double effect refrigeration system. (C) 2008 Elsevier Ltd. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐