Effects of inlet relative humidity and inlet temperature on the performance of counterflow wet cooling tower based on exergy analysis

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 49, 期 10, 页码 2795-2800

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2008.03.019

关键词

exergy analysis; wet cooling tower; exergy change; second law efficiency

资金

  1. Joint Graduate School of Energy and Environment (JGSEE)
  2. King Mongkut's University of Technology Thonburi
  3. Thailand Research Fund through the Royal Golden Jubilee Ph.D. Program [IUG50K0017]

向作者/读者索取更多资源

The purpose of this study is to analyze the influence of the ambient temperature and humidity on the performance of a counterflow wet cooling tower according to the second law, exergy analysis, of thermodynamics. First, the properties of water and air flow through the tower were predicted and validated by the experiment. Exergy analysis then has been carried out for investigating the cooling tower performance with various inlet air conditions, relative humidity and dry bulb temperature, while the water side condition is kept constant. According to the analysis in this paper, the similar result in terms of required dry air flow rate, exergy change of water and that of air, exergy destruction and second law efficiency were obtained for the various inlet air conditions. The exergy change of water Delta x(w) is higher than that of air Delta X-air, since Delta x(w) is the available energy of water to supply to air throughout the tower while Delta x(air), is the available energy of air to recover or utilize that supplied by water. It reveals that Delta x(air) is dominated by the exergy change of air due to evaporative heat transfer. In addition, it,gives a clearer explanation of the cooling tower performance and gives clear trends for optimization. (c) 2008 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据