4.7 Article

Integration of distributed generation systems into generic types of commercial buildings in California

期刊

ENERGY AND BUILDINGS
卷 40, 期 4, 页码 537-548

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2007.04.005

关键词

distributed generation; fuel cells; micro-turbine generators; photovoltaic arrays; emissions; absorption cooling; energy efficiency measures; load profiles; building energy simulation

向作者/读者索取更多资源

Distributed generation (DG) of combined cooling, heat, and power (CCHP) has been gaining momentum in recent years as an efficient, secure alternative for meeting increasing power demands in the world. One of the most critical and emerging markets for DG-CCHP systems is commercial and institutional buildings. The present study focuses analysis on the main economic, energy-efficiency, and environmental impacts of the integration of three types of advanced DG technologies (high-temperature fuel cells, micro-turbines, and photovoltaic solar panels) into four types of representative generic commercial building templates (small office building, medium office building, hospital, and college/school) in southern California (e.g., mild climate), using eQUEST as energy simulation tool. Detailed load profiles for the four commercial building types during times of peak electric and peak gas consumption were analyzed and complementary strategies to further increase overall building energy efficiencies such as energy efficiency measures (e.g., day lighting, exterior shading, improved HVAC performance) and thermally activated absorption cooling were also investigated. Results show that the high-temperature fuel cell (HTFC) performance is best matched with the hospital energy loads, resulting in a 98% DG capacity factor, 85% DG heat recovery factor, and $860,000 in energy savings (6 years payback). The introduction of thermally driven double-effect absorption cooling (AC) in the college building with HTFC reduces significantly the building electricity-to-thermal load ratio and boosts the heat recovery factor from 37% to 97%. (c) 2007 Published by Elsavier B.V.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据