4.7 Article

Saving energy in the make-up air unit (MAU) for semiconductor clean rooms in subtropical areas

期刊

ENERGY AND BUILDINGS
卷 40, 期 8, 页码 1387-1393

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2007.12.005

关键词

energy conservation; clean room HVAC system; make-up air unit (MAU)

向作者/读者索取更多资源

The energy requirements to cool, dehumidify, preheat and/or humidify outdoor air are significant in the make-up air unit (MAU) of clean room air-conditioning systems, and can represent 30% to 65% of the total thermal energy required to maintain a clean room environment. Because of these high-energy requirements, cost-effective means to reduce energy costs can influence unit production costs. Reducing or displacing mechanical cooling or electrical heating requirements can achieve the greatest opportunity for significant energy savings. This paper, therefore, aims to improve the energy performance of the MAU system by properly arranging compositions of components of a typical MAU applied in a semiconductor clean room. Explicitly, we investigated the influence of various factors including the fan location (draft-through type vs. push-through type), chilled water system (single-chilled water temperature system vs. two chilled water temperature system) and reheating scheme (electrical heating vs. hot water provided by heat recovery chiller). The result shows that the draw-through type accompanied by two chilled water temperature system with heat recovery function exhibits the lowest electrical power consumption. (C) 2008 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据