Experimental study on enhanced separation of a novel de-foulant hydrocyclone with a reflux ejector

期刊

ENERGY
卷 163, 期 -, 页码 490-500

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.energy.2018.07.166

关键词

Enhanced separation; Hydrocyclone; Reflux ejector; Suction angle; Sewage source heat pump

资金

  1. Provincial Science Foundation of Heilongjiang [E2017034]

向作者/读者索取更多资源

The novel de-foulant hydrocyclone (DFH) with reflux device can effectively remove foulant from sewage and prevent the heat exchanger of the sewage source heat pump from clogging. However, the geometry of the reflux device has not been investigated in detail. The underflow pipe of the reflux device may interfere with the decontamination performance. In this study, the reflux device was converted into a reflux ejector, which caused a sucking effect on the underflow of the DFH. For further study, the effects of the suction angle, shape of the suction pipe, and motive flow rate on the separation performance were investigated. The ratio of the underflow rate to the overflow rate was used as the eject coefficient of the reflux ejector. Results showed that the suction effect was the best at suction angle of 30 degrees; separation efficiency increased by 10% and the increase in energy consumption was less than 15 kPa compared with a suction angle of 90 degrees. Simultaneously, the suction effect, separation efficiency, and energy consumption increased with the increase of the motive flow rate, and the maximum energy consumption does not exceed 25 kPa. This means that changing the reflux ejector geometry can optimize the decontamination performance. (C) 2018 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据