4.7 Article

Corrosion management in power plant cooling systems using tertiary-treated municipal wastewater as makeup water

期刊

CORROSION SCIENCE
卷 61, 期 -, 页码 231-241

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.corsci.2012.04.042

关键词

Alloy; Copper; Mild steel; Polarization; Weight loss; Pitting corrosion

资金

  1. US Department of Energy, National Energy Technology Laboratory [DE-FC26-06NT42722, DE-NT0006550]
  2. International Fulbright Science and Technology Award

向作者/读者索取更多资源

Additional tertiary treatment of secondary-treated municipal wastewater (MWW) is necessary to reduce its scaling potential for use in power plant cooling systems. In this study corrosiveness of three tertiary-treated municipal wastewaters (acidified MWW, MWW treated by nitrification-filtration, and MWW treated by nitrification-filtration and granular activated carbon adsorption) towards mild steel, copper, and cupronickel alloys was assessed. pH, ammonia, and organic matter were identified as important corrosion influencing parameter in tertiary-treated municipal wastewater. Corrosiveness of wastewater towards metal alloys increased after tertiary treatments. However, corrosion of mild steel and copper alloys was controlled within acceptable limits using the corrosion inhibitor tolyltriazole. (C) 2012 Elsevier Ltd. All rights reserved.