期刊
APPLIED THERMAL ENGINEERING
卷 51, 期 1-2, 页码 334-337出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2012.09.008
关键词
Condenser; Metal foam; Louvered fin; Microchannel; Refrigeration
资金
- FINEP
- CNPq [573581/2008-8]
Experimental work was conducted to compare the thermal hydraulic performances of cross-flow microchannel condensers using louvered fins and metal foams as extended surfaces. Three copper foam surfaces with pore densities of 10 and 20 pores per inch (PPI) and porosities of 89.3 and 94.7%, and three aluminum louvered fins with lengths of 27 and 32 mm (in the flow direction) and heights of 5 and 7.5 mm were evaluated. The experiments were carried out in a closed loop wind-tunnel calorimeter equipped with a R-600a refrigeration loop. A condensing temperature of 45 degrees C was used in all tests, with face velocities ranging from 2.1 to 7.7 m/s. A comparison based on the thermal conductance and air-side pumping power showed that the surfaces enhanced with louvered fins performed better than the metal foams under all conditions investigated. (C) 2012 Elsevier Ltd. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐