Experimental energetic analysis of a vapor compression refrigeration system with dedicated mechanical sub-cooling

期刊

APPLIED ENERGY
卷 102, 期 -, 页码 1035-1041

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2012.06.007

关键词

Subcooling; Experiment; Refrigeration; R12; R22

资金

  1. King Abdulaziz City for Science and Technology (KACST) through the Science & Technology Unit at King Fand University of Petroleum & Minerals (KFUPM) as part of the National Science, Technology and Innovation Plan [NSTIP-08-ENE50-4]

向作者/读者索取更多资源

In this work, an experimental investigation into the effects, in terms of energy, of employing a dedicated mechanical subcooling cycle with a residential 1.5 ton simple vapor compression refrigeration system is presented. A comparative analysis of the experimental cycle performance is conducted with and without the dedicated subcooler cycle when the room temperature is kept between 18 and 22 degrees C. This is done in order to ascertain the percentage increase in efficiency due to use of a dedicated subcooling loop. R22 is employed as the refrigerant in the main cycle whereas R12 is flowing in the dedicated subcooling cycle. The experimental outcomes indicate that the load carrying capacity of the evaporator increased by approximately 0.5 kW when R22 was subcooled, in the main cycle, by 5-8 degrees C. It was also noted that, by using the subcooling, the second-law efficiency of the cycle increased by an average of 21%. Furthermore, the general trend indicated that this percentage increase is inversely proportional to the ambient temperature variation. The experimental work proves that dedicated subcooling can be used for increasing cooling capacity and efficiency. (c) 2012 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据