期刊
APPLIED THERMAL ENGINEERING
卷 142, 期 -, 页码 321-333出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2018.07.005
关键词
Heat pipe; Thermosyphon loop; Two-phase natural loop; Pump-driven loop; Experiment
资金
- National Natural Science Foundation of China [51638010]
- Innovative Research Groups of the National Natural Science Foundation of China [51521005]
Two-phase natural loops (TPNLs) have been widely used in HVACs for energy conservation. Under harsh conditions, a mechanical pump is usually added in the loop (TPPLs), which is expected to enhance the performance. Unfortunately, the extent and reasons for the enhancement is unclear owing to a lack of comparative studies between TPNLs and TPPLs. In this study, an experimental setup that includes both TPNL and TPPL was established, which were measured comparatively for five typical cases. The results indicate that: (1) When a TPNL performs poorly (under-charged refrigerant, over-charged refrigerant, or insufficient height difference), a pump can enhance the performance remarkably (up to 400%), approaching the ideal cycle of TPNL, and the main contribution to the enhancement is eliminating the overheating and sub-cooling, rather than increasing heat convection. (2) For a well-designed TPNL, the pump cannot further enhance the performance, and the pump is unnecessary. (3) When the flow resistance is considerable, the pump even degrades the performance owing to a considerable pressure drop. Finally, (4) the ideal cycle of TPNL is the boundary of the enhancement, and the application principle of the pump is to approach the ideal cycle at as low a speed as possible.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据