Limitations of the use of concrete bulk resistivity as an indicator for the rate of chloride-induced macro-cell corrosion

期刊

STRUCTURAL CONCRETE
卷 18, 期 2, 页码 326-333

出版社

ERNST & SOHN
DOI: 10.1002/suco.201500141

关键词

chloride-induced corrosion; concrete resistivity; corrosion rate

资金

  1. Norwegian Public Roads Administration

向作者/读者索取更多资源

An experimental setup was designed to study the impact of concrete bulk resistivity on the rate of chloride-induced reinforcement corrosion. Small pieces of mild steel were used to simulate pits (anodes) that form when chlorides come into contact with the reinforcement. The galvanic current was measured between the simulated anodes and a large cathode network. Comparisons were made between the corrosion rates calculated from the galvanic currents and the bulk resistivity. The bulk resistivity was varied using two mortar mixes (made of plain Portland cement and a Portland cementfly ash blend), which were exposed in different temperature and moisture conditions. Despite a high scatter in the results, it was clear that the relationship between bulk resistivity and corrosion rate depended on the mortars tested. The findings presented in this article and the accompanying work strongly indicate that bulk resistivity alone does not provide sufficient information for assessment of the corrosion rate for chloride-induced macro-cell corrosion.