Heat removal capacity of laminar coolant flow in a micro channel heat sink with different pin fins

期刊

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.ijheatmasstransfer.2017.05.106

关键词

-

资金

  1. National Natural Science Foundation of China [51305265]
  2. Major State Basic Research Development Program of China [613204]

向作者/读者索取更多资源

Micro channel heat sinks with staggered pin fins are designed and studied in this paper. Three typical pin fins (rhombus, hydrofoil and sine) with symmetry geometries and low flow resistance were made a detailed comparison in the study. Simulations indicate that the heat sink with sine pin fins shows the best heat removal capacity and the lowest pressure drop when the coolant flow rate is 100 ml/min and the heating flux is 144 W/cm(2). Chip's hottest points are 357.90 K, 356.81 K and 354.91 K in the three cases and the pressure drops between the inlet and the outlet are 15793.50 Pa, 15242.21 Pa and 15196.04 Pa respectively. The same trend exists among the obtained experimental results and theoretical simulations. The research systematically studied the pin fins' influence to the heat sink by simulation and confirmed the conclusion by experiment. This method can be used in the following research about the heat sink. The study also found the best pin fins configuration of the three typical structures, and the structure will be helpful for the heat sinks design. (C) 2017 Published by Elsevier Ltd.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据