4.5 Article

Numerical Analysis of the Hot-spot Temperature of a Power Transformer with Alternative Dielectric Liquids

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TDEI.2017.006228

关键词

Power transformer; thermal modelling; conjugate heat transfer; alternative dielectric liquids; hot-spot temperature

资金

  1. Spanish Ministry of Science [DPI2013-43897-P]
  2. University of Cantabria
  3. Government of Cantabria [CVE-2015-11149]

向作者/读者索取更多资源

The assessment of two vegetal oils as coolant in Low Voltage Winding of a power transformer with zigzag cooling have been analyzed. These dielectric fluids cooling performance has been compared with a typical mineral oil. To make the study, a 2D-axisymmetrical model of a power transformer has been developed to perform a numerical analysis using a Finite Element Method based software, COMSOL Multiphysics (R). Some values are obtained in order to establish the comparison, such as hot-spot temperature or hot-spot factor. Moreover, the influence of the increase of the number of passes of the cooling circuit on the hot-spot temperature has been evaluated for all liquids and compared with the initial design. Results obtained in this work show that the hot-spot temperature is lower for the vegetal oils in the initial design. Furthermore, an increase in the number of passes affect more positively to the mineral oil since similar values of the hot-spot temperature for all liquids are obtained. Values of the hot-spot factor indicates that higher number of passes leads to lower efficient cooling circuits owing to the increase of the pressure drop although the hot-spot temperature decreases.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据