4.5 Article

Experimental investigation on the thermodynamic performance of double-row liquid-vapor separation microchannel condenser

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2016.02.020

关键词

Double-row liquid-vapor separation microchannel condenser; Thermodynamic performance; Penalty factor; Minimum entropy generation number

资金

  1. Guangzhou Science and Technology Plan Project [7411804865260]

向作者/读者索取更多资源

A double-row liquid-vapor separation microchannel condenser (D-LSMC) was presented, and its tube pass scheme was optimized using the theoretical method. A series of experiments were conducted to investigate the heat load, average heat transfer coefficient (AHTC), and pressure drop of the optimal D-LSMC. Experimental results were compared with an optimal common double-row parallel-flow microchannel condenser (D-PFMC). The findings showed that, at the inlet mass flux of 585 kgm(-2) s(-1) to 874 kgm(-2) s(-1), the AHTC of the D-LSMC was 3.3%-14.4% higher than that of the D-PFMC. However, the pressure drop of the D-LSMC was only 43.4%-52.1% of that of the D-PFMC. The heat exchange capacity of the back row was weaker by almost half of that of the front row. In addition, the tube wall temperature of the back row decreased faster than that of the front row, which indicated that the back row had a larger pressure drop. The minimum entropy generation number (Ns) was used to evaluate the D-LSMC and the D-PFMC, which indicated the greater thermodynamic performance of the D-LSMC. (C) 2016 Elsevier Ltd and IIR. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据