Impact of inductive current transformers on synchrophasor measurement in presence of modulations

期刊

MEASUREMENT
卷 155, 期 -, 页码 -

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.measurement.2020.107535

关键词

Current transformer (CT); Power system measurements; Synchrophasor measurement; Phasor measurement unit (PMU); Amplitude modulation; Phase modulation; Frequency modulation

资金

  1. EMPIR - European Metrology Programme for Innovation and Research (EMPIR) within EURAMET, Germany [17IND06]
  2. EMPIR within European Union [17IND06]

向作者/读者索取更多资源

Instrument Transformers (ITs) are essential devices for all the measurement tasks, f.i. metering, protection and diagnostics, in electricity grids, since they scale voltage and current down to levels compatible with measuring instruments. At the input of Power Quality (PQ) instruments and Phasor Measurement Units (PMUs), inductive voltage and current transformers (VTs and CTs) are still the most used ITs, even if, their performance in presence of disturbances is not fully assessed. This paper analyses the impact of the inductive CTs on the measurement of fundamental synchrophasors, by a PMU, in presence of a particular class of disturbances, the undesired modulations on current signals. Experimental tests, on two different CTs, show that there are critical situations, where, even compensating CT systematic ratio and phase errors, 1) CT exceeds its accuracy class limit and 2) considering the sole contribution of CT, PMU performance stays very close to the error limits of the standards. (C) 2020 The Author(s). Published by Elsevier Ltd.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据