4.7 Article

On identifying steady-state parameters of an experimental mechanical-compression refrigeration plant

期刊

APPLIED THERMAL ENGINEERING
卷 109, 期 -, 页码 318-333

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2016.08.021

关键词

Refrigeration system; Vapour compression; Identification method; Phase-change heat exchanger

资金

  1. MCeI [DPI2015-70973-R, DPI2013-44135-R]

向作者/读者索取更多资源

This paper describes the thermodynamic model of a vapour compression refrigeration system, focusing on the performance of the heat exchangers. A novel steady-state identification method is proposed, which is based on inaccessible refrigerant phase-change zones assuming that a constant overall heat transfer coefficient can be identified for each zone. The proposed method has been applied to a configurable two-stage, two-load-demand vapour compression refrigeration plant. Considering steady-state experimental data and taking into account orders of magnitude of the global heat transfer coefficients found in the literature, some relationships between them and the heat exchanger zone lengths are suggested. Then coherent values are obtained for all heat transfer coefficients, which confirms the validity of the hypothesis. Additionally the remaining elements of the refrigeration system have been identified using well-known models. Experiments have been carried out in order to validate this method, using a one-stage, two-load-demand configuration. Although all components are separately identified, a global validation method is implemented, of which results show good agreement with experimental data, with relative estimation errors around 10% in the key variables. (C) 2016 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据