Full-scale experimental and numerical analysis of water mist system for sheltered fire sources in wind generator compartment

期刊

出版社

INST CHEMICAL ENGINEERS
DOI: 10.1016/j.psep.2015.05.011

关键词

Full-scale fire experiments; Numerical simulations; Water mist system; Wind generators; Sheltered fire sources; FDS

资金

  1. Ministry of Science and Technology of Taiwan, Republic of China [MST-101-2625-M-261-001-MY3]

向作者/读者索取更多资源

Through a series of full-scale fire experiments and numerical simulations, the effectiveness of water mist system on wind generator could be estimated, and compared with fire parameters, such as exposed or unexposed fire sources, number of nozzles, un-sheltered or sheltered fire sources, and fire source location. The experimental study found that the position of the water mist nozzles and whether the flames inside the oil pan are covered have a significant influence on overall extinguishing efficacy. The water mist system proved to have sound effectiveness on fire suppression in wind generators with sheltered fire source. According to FDS simulations of water mist systems, the simulated temperature curve declined more significantly than that for the actual measurements, indicating that the cooling effect of the simulated water mist was better. However, simulations were used for a situation where water mist was unable to directly extinguish the fire. Analysis of the simulated airflow showed that an opening caused the water to discharge outwards and the airflow was disturbed by the outside; thus, the extinguishing effect was poorer. There was less water with a sheltering object, and thus the extinguishing effect was poorer. (C) 2015 The Institution of Chemical Engineers. Published by Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据