4.5 Article

Experimental study of high strength concrete-filled circular tubular columns under eccentric loading

期刊

JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH
卷 67, 期 4, 页码 623-633

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.jcsr.2010.11.017

关键词

Composite column; Concrete-filled tubular columns; High strength concrete; Buckling

资金

  1. Spanish Ministry of Education [BIA2005_255, BIA 2009_09411]
  2. European Community

向作者/读者索取更多资源

The paper describes 37 tests conducted on slender circular tubular columns filled with normal and high strength concrete subjected to eccentric axial load. The test parameters were the nominal strength of concrete (30, 70 and 90 MPa), the diameter to thickness ratio D/t, the eccentricity ratio e/D and the column slenderness (L/D). The experimental ultimate load of each test was compared with the design loads from Eurocode 4, which limits the strength of concrete up to 50 MPa. The aim of the paper is to establish the advisability of the use of high strength concretes as opposed to that of normal strength concretes by comparing three performance indices: concrete contribution ratio, strength index and ductility index. The results show for the limited cases analyzed that the use of high strength concrete for slender composite columns is interesting since this achieves ductile behavior despite the increase in load-carrying capacity is not greatly enhanced. (C) 2010 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据