FIRE SAFETY ASPECTS OF REFUGE FLOORS IN SUPERTALL BUILDINGS WITH COMPUTATIONAL FLUID DYNAMICS

期刊

JOURNAL OF CIVIL ENGINEERING AND MANAGEMENT
卷 15, 期 3, 页码 225-236

出版社

VILNIUS GEDIMINAS TECH UNIV
DOI: 10.3846/1392-3730.2009.15.225-236

关键词

refuge floor; supertall buildings; evacuation; fire safety provisions

向作者/读者索取更多资源

High-rise buildings in many big cities in the Far East, including Hong Kong, call for refuge floors as a matter of both practicality and compliance with regulations. Even though many countries' fire codes are not clear in spelling out the necessity for refuge floors, it is accepted within construction that such floors are essential in resisting fire, allowing users a means of escape and allowing emergency services a means of access to stricken buildings. This paper discusses the reasons behind providing refuge floors, while also considering related fire safety provisions, such as their enclosure behind fire-resistant construction or the protection of their openings behind a water curtain. Our discussion takes a tall building with balconies as a test example of refuge floors, running a hazard assessment based on Computational Fluid Dynamics assuming a fire of the broadly accepted level of 2 MW. The paper concludes that the design of the building's facade finally determines whether or not a refuge floor and associated fire safety provisions, such as a water curtain, can be waived. As the flat modelled used to store a high amount of combustibles up to 1135 MJm(-2), the breaking of large area of glass window could lead to a major conflagration. The consequences of a scenario with a fire of 25 MW are also discussed.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据