期刊
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
卷 33, 期 8, 页码 1657-1669出版社
ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2010.05.002
关键词
Thermal storage; Ice bank; Cooling; Milk; Experiment; Modelling; Simulation; Comparison
In order to verify the mathematical model of an ice bank system developed for the purpose of predicting the system performance, experimental measurements on the ice bank system were performed. Static, indirect, cool thermal storage system, with an external ice-on-coil building/melting was considered. Cooling energy stored in the form of ice by night is used for the rapid cooling of milk after the process of pasteurization by day. The ice bank system was tested under real operating conditions to determine parameters such as the time-varying heat load imposed by the consumer, refrigeration unit load, storage capacity, supply water temperature to the load and to find charging and discharging characteristics of the storage. Experimentally obtained results were then compared to the computed ones. It was found that the calculated and experimentally obtained results are in good agreement as long as there is ice present in the silo. (C) 2010 Elsevier Ltd and IIR. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐