期刊
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
卷 32, 期 2, 页码 235-245出版社
ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2008.06.003
关键词
HFE-7100; Secondary refrigerant; Experiment; Heat transfer; Critical heat flux; Pool boiling; Geometry; Channel
资金
- MIUR [COFIN 2004098758]
Experiments were performed to examine the pool boiling heat transfer and critical heat flux on a smooth copper circular surface, confined by a face-to-face parallel unheated surface, by changing both the orientation and the gap between the surfaces. Pool boiling data at atmospheric pressure were obtained for saturated HFE-7100. The gaps between the boiling surface and adiabatic one were 0.5, 1.0, 2.0, 3.5, 5.0, 10.0 and 20.0 mm. For each configuration, boiling curves were obtained up to the thermal crisis. The surface orientations investigated were 0 degrees (horizontal upward surface), 45 degrees, 90 degrees and 135 degrees. It was observed that the heat transfer coefficient improves at low wall superheat when the distance between heated and unheated surfaces decreases. However, at high wall superheat, a drastic reduction in heat transfer as well as CHF appears for confined boiling. For a fixed channel width, the CHF value strongly depends on the channel orientation, assuming a maximum value for near-vertical channels with up-facing heated surface. CHF data were compared with various literature correlations; a new empirical correlation that takes into account channel gap effects is proposed for horizontal confined surfaces. (C) 2008 Elsevier Ltd and IIR. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐