4.7 Article

A parameter study of tube bundle heat exchangers for fouling rate reduction

期刊

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.ijheatmasstransfer.2014.01.010

关键词

Particulate deposit; Heat exchanger; Heat transfer; Pressure drop; Numerical simulation

资金

  1. National Key Basic Research Program of China (973 Program) [2013CB228304]
  2. Specialized Research Fund for the Doctoral Program of Higher Education [20120201130006]
  3. Research Project of Chinese Ministry of Education [113055A]

向作者/读者索取更多资源

The formation of particulate deposits on flue gas heat exchanger surfaces will reduce heat transfer efficiency, increase the instability of equipment operation and introduce a major uncertainty into the heat exchanger design. In this paper, a numerical model was developed to predict the flue-ash particle deposition rate by considering particles transport, sticking and rebound behaviors based on the software FLUENT, extended by user-defined functions (UDFs). The numerical model was applied to cross-flow tube bundle heat exchangers with a 6-row tube arrangement. The effects of six parameters (particle diameter, flow velocity, spanwise tube pitch, longitudinal tube pitch, tube geometry shape, and arrangement) on fouling rate, as well as on the heat transfer and hydrodynamics performance, were examined. It was found that particle deposits accumulated primarily in the flow stagnation region, recirculation region, the vortex separation and reattachment regions. Increasing particle diameter moved the deposition zones towards the windward side of tubes. Using both oval tubes and staggered arrangements can reduce the fouling rate. With the increase in longitudinal tube pitch, both the particulate deposit rate and the heat transfer performance increased. To account for fouling and heat transfer performance, a tube spacing value of 2 was recommended. (c) 2014 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据