4.7 Article

Thermoeconomic analysis of ground-source heat pump systems

期刊

INTERNATIONAL JOURNAL OF ENERGY RESEARCH
卷 38, 期 2, 页码 259-269

出版社

WILEY
DOI: 10.1002/er.3024

关键词

ground source; heat pump; thermoeconomic analysis

资金

  1. Electric Power Public Tasks Evaluation & Planning Center of Korea

向作者/读者索取更多资源

A thermoeconomic analysis of a ground-source heat pump (GSHP) system with a vertical or horizontal ground heat exchanger, a type of heat delivery system, was performed using the modified productive structure analysis method. In this analysis, the unit cost of geothermal heat delivered to a room using GSHP system was estimated. The unit cost of heat delivered was calculated to be $0.063/kWh for input of electricity with a unit cost of $0.140/kWh for a GSHP with a coefficient of performance (COP) of 3.27. Exergy destruction and monetary losses due to the irreversibility that occurs at each component of the system were also estimated. The unit cost of heat was found to be inversely proportional to the COP of the heat pump and proportional to the electricity input. The greatest monetary loss occurs in the geothermal heat exchanger in which considerable mass of brine flows in long pipes and in the fan-coil unit which features a complex configuration of pipes in the air passages, respectively. Copyright (c) 2013 John Wiley & Sons, Ltd.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据