4.6 Article

Failure Risk of UHV AC Transmission Line Considering the Statistical Characteristics of Switching Overvoltage Waveshape

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 28, 期 3, 页码 1731-1739

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2013.2252238

关键词

Failure risk; switching overvoltage; transmission line; ultra-high-voltage (UHV) AC system; wavefront time; waveshape

资金

  1. National Natural Science Foundation of China [5073001]
  2. National Basic Research Program of China (973 Project) [2009CB724504]
  3. China State Power Grid

向作者/读者索取更多资源

The sizes of ultra-high-voltage (UHV) towers and substations are related to the air clearances which are usually determined by switching overvoltage. Based on electromagnetic transient simulation of the first 1000-kV UHV ac transmission line in China, this paper extracted the effective wave information in accordance with the concept of the active part of the waveshape from calculated main types of switching overvoltage. Moreover, based on test results of switching impulse flashover voltages, a practical and accurate method to calculate the risk of failure was presented, which considered the variable characteristics of the insulation strength of the transmission line under different switching overvoltage waveshapes. Evaluation of the results focused on the comparison between two new methods and the traditional simplified method considering the effect of the front time.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据